CHAPTER 10 - LIGHTING AND VENTILATION
10-1. Size of external openings
10-1.1. Every room, other than rooms used predominantly for the
storage of goods, shall be provided with natural light and natural
ventilation by means of one or more openings in external walls.
These openings shall have a combined area of not less than 10%
for habitable rooms and 7.5% for other rooms of the floor space
of such opening, and the whole of such openings shall be capable
of allowing free and uninterrupted passage of air.
10-1.2. Area for openings in case of warehouse, godown, storage
places etc. shall not be less than 5% of the floor space unless
the space is mechanically ventilated.
10-2. Size of internal openings
Unless the light and ventilation requirements are met by an air
well or ventilation duct, all internal habitable rooms must have
openings in internal air wells in addition to door openings not
less than 7.5% of the floor area of such room. Access for maintenance
of shaft be provided at level for where the shaft is commence.
10-3. Internal Air Wells
10-3.1. Habitable rooms may receive daylight and natural ventilation
from internal air wells which shall conform with the following
minimum sizes:-
10-3.1.1. For buildings up to 2 storeys, 50Sq.ft..(4.6Sq.m) with
minimum width of well 5ft.(1.5m).
10-3.1.2. For buildings with 3 to 5 storeys, 100Sq.ft..(9.3Sq.m)
with minimum width of well 8ft.(2.44m).
10-3.1.3. For buildings higher than 5 storeys, 100Sq.ft..(9.3Sq.m)
plus 10Sq.ft.(0.93Sq.m) for each additional floor over 5 storeys
and minimum width of well 10ft.(3.0m).
10-3.2. Where only kitchens, W.C.’s and bathrooms receive
daylight and ventilation from air-wells, their sizes shall conform
with the following as minimum:-
10-3.2.1. For buildings up to 2 storeys, 25Sq.ft.(2.3Sq.m) with
minimum width of well 3ft.(0.9m).
THE SINDH GOVT. GAZETTE APRIL 04, 2002 474
10-Lighting and Ventilation
10-3.2.2. For buildings with 3 to 5 storeys, 50Sq.ft.(4.6Sq.m)
with minimum width of well 5ft.(1.5m).
10-3.2.3. For buildings higher than 5 storeys, 50Sq.ft.(4.64Sq.m)
plus 5Sq.ft.(0.46Sq.m) for each additional floor with minimum
width of well 5ft.(1.5m).
10-3.3 Access for maintenance of each such shaft shall be provided
at lowest level of the shaft.
10-4. Permanent Openings in Kitchen
Every kitchen shall have openings for permanent ventilation into
the external air space not less than 15% of its floor area.
10-5. Water Closet, Bath Room & Ablution Places.
Every water closet, urinal stall, and bath room and ablution
area shall be provided with natural lighting and ventilation by
means of one or more openings in external walls having a combined
area of not less than 2Sq.ft.(0.2sq.m) per water closet, urinal
or bathroom except where adequate and permanent mechanical ventilation
is provided and which discharges into an open space.
10-6. Garages
Every garage shall be provided with opening of not less than
5% of the floor area for ventilation and lighting incorporated
in a wall or in the door.
10-7. Staircases
All staircases which are enclosed shall be provided with adequate
lighting and ventilation from openings not less than 7.5% of the
staircase area.
10-8. Mechanical Ventilation and Central Air-Conditioning waiver
& minimum requirement.
10-8.1. Where undertaking for central air-conditioning and permanent
mechanical ventilation is provided, the relevant clauses of these
Regulations dealing with natural ventilation, lighting and heights
of rooms may be waived.
10-8.2. Where permanent mechanical ventilation in respect of
lavatories, water closets, bath rooms or corridors has been provided
for and maintained in accordance with the following clauses, conditions
relating to natural ventilation and natural lighting under these
Regulations shall not apply to such lavatories, water-closets,
bathrooms or corridors.
THE SINDH GOVT. GAZETTE APRIL 04, 2002 475
10-Lighting and Ventilation
10-8.3. Basement or underground car parks and other enclosures
below ground level shall be provided with mechanical ventilation.
10-8.4. Cinemas or other projection rooms where photographic
film is being used, processed or stored; which are situated in
the internal portion of the building; and in respect of which
no such external walls (or those overlooking verandahs, pavements
or walkways) are present, shall be provided with mechanical ventilation
or air conditioning.
10-8.5. In case of mechanical ventilation and central air conditioning
for all types of buildings and spaces HVAC relevant code of practice
as may be approved by the Authority shall be followed.
|